Type |
Name
|
Application | |
Cu Conductor |
Al Conductor |
||
YJV YJY |
YJLV YJLV |
XLPE Insulated,PVC or PE S heathed Power Cable | For laying in door,tunnel,channel and underground.Unable to bear external mechanical force,but bear the traction force during laid. |
YJV22 YJV23 |
YJLV22 YJLV23 |
XLPE Insulated,Steel Tape Armoured,PVC or PE Sheathed Power Cable |
For laying in tunels in door,tunnel,channel and underground.Able to bear external mechanical force,but unable to bear large pulling force. |
YJV32 YJV33 |
YJLV32 YJLV33 |
XLPE Insulated,Fine Steel Wire Armoured,PVC or PE Sheathed Power Cable |
For laying in shaft with large difference of level.Able to bear external mechanical force,and moderable pulling force. |
YJV42 YJV43 |
YJLV42 YJLV43 |
XLPE Insulate,Thick Steel Wire Armoured,PVC or PE Sheathed Power Cable |
Able to bear positive pressure and pulling force |
Power cables for power networks, underground, outdoors and in cable ducting.
Standards:BS6622
Conductor:Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)
Conductor screen:Semi-conducting material
Insulation:XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen:Semi-conducting material
Metallic Screen:Individual and overall copper tape screen to BS6622
Filler:PETP (Polyethylene Terephthalate) fibres
Separator:Binding tape
Bedding:PVC (Polyvinyl Chloride) Type TM1 to BS7655
Armouring:Single Core: Aluminium Wire Armoured (AWA)
Multi-core: Steel Wire Armoured (SWA)
Sheath:PVC (Polyvinyl Chloride) Type TM1 to BS7655
Colour:Red or Black
Voltage Rating:19000/33000V
Temperature Rating:0°C to +90°C