Bare Conductor

Contact Us

  • Email:  sales@hlcables.com
  • Tel:    86-371-66766667
  • WhatsApp:    +86-15093102503
  • Office:    Nanpu International Center, Jinshui dustrict, Zhengzhou City,China.
  • Factory:    YunXiang East Road, Xiuwu Industry, Jiaozuo City.

AAAC aluminum alloy conductor cable

Bare Overhead Conductors

STANDARDS

National :  ASTM B 399;ASTM B 399

DESCRIPTION

Bare all aluminum alloy conductors (AAAC) are concentric-lay-stranded consisting of aluminum alloy 6201 wires wrapped helically around a central wire.  The aluminum is heat-treated to a T81 temper to provide superior strength.

Features and Benefits
AAAC conductors provide a higher strength to weight ratio than traditional AAC conductors, and better corrosion resistance than ACSR conductors.

Applications
Stranded bare AAAC may be used for overhead line installations where the higher strength or temperature ratings of ACSR, ACCR or other types of conductors is not required, but improved sag performance to AAC is desired.

ALL ALUMINUM ALLOY CONDUCTORS (AAAC) PHYSICAL DATA

Codeword

 Size
(kcmil)

No. of 
Wires

Nominal Diameter (in.)

ACSR with 
Equal Diameter

Approx. AAC 
with Equal 
Resistance

Nominal
Weight
(lb/kft)

Rated 
Strength 
(lbf)

Individual
Wires

Complete 
Conductor

Size 
(AWG)

Stranding

Alton

48.69

7

0.0834

0.250

4

6/1

4

45.4

1760

Ames

77.47

7

0.1052

0.316

2

6/1

2

72.2

2800

Azusa

123.3

7

0.1327

0.398

1/0

6/1

1/0

114.9

4270

Anaheim

155.4

7

0.1490

0.447

2/0

6/1

2/0

144.9

5390

Amherst

195.7

7

0.1672

0.502

3/0

6/1

3/0

182.5

6790

Alliance

246.9

7

0.1878

0.563

4/0

6/1

4/0

230.2

8560

ALL ALUMINUM ALLOY CONDUCTORS (AAAC) ELECTRICAL DATA

Codeword

 Size
(kcmil)

No. of 
Wires

Resistance 
(ohm/kft)

Ampacity*
(A)

DC at 20°C

AC at 75°C

Alton

48.69

7

0.414

0.492

143

Ames

77.47

7

0.260

0.311

191

Azusa

123.3

7

0.164

0.195

256

Anaheim

155.4

7

0.130

0.155

296

Amherst

195.7

7

0.103

0.123

342

Alliance

246.9

7

0.0816

0.0973

395

* Based on 75°C conductor temperature, 25°C ambient temperature, in sun and wind at 2 ft/sec.